Command devices
Stop button ((N.C.) contact.)
- Door stopping button that excludes the automatic closing.To resume movement
press the command button or trasmitter key.
If unused set DIP switch n.9 to ON.
Ket switch selector and/or opening button (N.O. contact)
- Door opening command.
Key-switch selector and/or opening button ( N.O. contact) -
Door opening and closing commands, by pressing the button
or turning the selector key,
or stops depending on what is selected on the Dip-switches
(see selecting functions, Dip-switches 2 and 3). Jumper OFF
(p. 4 point 20) .
Key switch selector and/or opening button (N.O. contact) - Door
closing command.
Jumper ON (p. 4 point 20).
6.1 Electrical connection for photocells functionalities test
(Delta)
With each opening and c
losing command, the card checks the effi ciency of the safety devices
(i.e. photocells). Any anomalies
in the photocell is notifi ed by the fl ashing
LED (PROG) on the control panel, and cancels any other command from the transmitter or button.
Electrical connection to work the photocells safety test:
- the transmitter and receiver, must connected as shown in the diagram:
Set Dip-switch 3 (Four-way Dip-switch) to ON to activate the test.
IMPORTANT:
When you activate the safety test, CHECK that THERE ARE NO JUMPER BRIDGES between contacts 2-C3, 2-C1 and, if the contacts are
unused, exclude them via Dip-switch 8 and 10.
the door inverts its movement
(DIR)