AERMEC ANK 설치 매뉴얼 - 페이지 4
{카테고리_이름} AERMEC ANK에 대한 설치 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. AERMEC ANK 14 페이지.
This heat pump is shipped in one package, completely
assembled and wired. The indoor controller is shipped in a separate
carton when ordered.
1. Check the heat pump rating plate to confirm specifications
are as ordered.
2. Upon receipt of equipment, carefully inspect it for possible
shipping damage. Take special care to examine the unit
inside the carton if the carton is damaged.
If damage is found, it should be noted on the carrier's freight bill.
Damage claims should be filed with the carrier immediately.
Claims of shortages should be filed with the seller within 5 days.
NOTE: If any damages are discovered and reported to the carrier,
do not install the unit because your claim may be denied.
2.1 HYDRONIC CONNECTIONS
Water / glycol piping must be connected by a licensed, or certified
technician using established procedures.
IMPORTANT:
Connecting water lines must be clean, properly sized
(minimum 1 ¼ inch). Reducing fitting shall not be used
Use care with the water / glycol lines during the installation
process. If pex is used it can be cut by sharp objects.
Do not remove the caps from the lines or system connection
points until connections are ready to be completed.
1. Route the supply and return lines from the fittings on the
indoor manifold or tank to the fittings on the heat pump. Run
the lines in as direct a path as possible avoiding unnecessary
turns and bends.
2. Ensure that both lines are insulated over the entire
exposed length and that both supply and return lines are not
in direct contact with floors, walls, duct work, floor joists, or
other piping.
3. Flush the lines out with water
4.Pack insulating material around water/glycol lines where they
penetrate the structure to protect the lines and to minimize
vibration transmission.
5. Connect the supply and return lines, and tighten using two
wrenches
NOTE: Always use two wrenches when tightening any fittings.
4
2 INSTALLATION INSTRUCTIONS
ANK 030‐045‐050 H‐HP
Air vent
ANK 030‐045‐050 HA
Air vent
Air vent