AERMEC ANK Руководство по установке - Страница 4

Просмотреть онлайн или скачать pdf Руководство по установке для Охладитель AERMEC ANK. AERMEC ANK 14 страниц.

AERMEC ANK Руководство по установке
This heat pump is shipped in one package, completely 
assembled and wired. The indoor controller is shipped in a separate 
carton when ordered. 
1. Check the heat pump rating plate to confirm specifications 
are as ordered. 
2. Upon receipt of equipment, carefully inspect it for possible 
shipping damage. Take special care to examine the unit 
inside the carton if the carton is damaged. 
If damage is found, it should be noted on the carrier's freight bill. 
Damage claims should be filed with the carrier immediately. 
Claims of shortages should be filed with the seller within 5 days. 
NOTE: If any damages are discovered and reported to the carrier, 
do not install the unit because your claim may be denied. 
2.1 HYDRONIC CONNECTIONS 
Water / glycol piping must be connected by a licensed, or certified  
technician using established procedures. 
IMPORTANT: 

Connecting water lines must be clean, properly sized 
   (minimum 1 ¼ inch). Reducing fitting shall not be used 

Use care with the water / glycol lines during the installation 
process. If pex is used it can be cut by sharp objects. 

Do not remove the caps from the lines or system connection 
points until connections are ready to be completed. 
 1. Route the supply and return lines from the fittings on the 
indoor manifold or tank to the fittings on the heat pump. Run  
the lines in as direct a path as possible avoiding unnecessary  
turns and bends. 
 2. Ensure that both lines are insulated over the entire 
exposed length and that both supply and return lines are not 
in direct contact with floors, walls, duct work, floor joists, or 
other piping. 
 3. Flush the lines out with water 
4.Pack insulating material around water/glycol lines where they 
penetrate the structure to protect the lines and to minimize 
vibration transmission. 
5. Connect the supply and return lines, and tighten using two    
wrenches 
NOTE: Always use two wrenches when tightening any fittings. 
 
4  

2 INSTALLATION INSTRUCTIONS

ANK 030‐045‐050 H‐HP 
Air vent 
ANK 030‐045‐050 HA 
Air vent 
Air vent