AERMEC ANK Руководство по установке - Страница 3
Просмотреть онлайн или скачать pdf Руководство по установке для Охладитель AERMEC ANK. AERMEC ANK 14 страниц.
1.6 ELECTRICAL REQUIREMENTS
3
IMPORTANT:
Electrical wiring, disconnect means and over current
protection are to be supplied by the installer. Refer to the
rating plate for the maximum over current protection,
minimum circuit ampacity, and operating voltage. See wiring
diagram.
Install an adequately sized branch circuit disconnect, per the
NEC, within sight of and readily accessible from heat pump.
The cable or conduit and fittings connected from the
disconnect to the heat pump shall be rated for outdoor use.
Check the heat pump rating plate and follow the
appropriate instructions below.
NOTE: All wiring must be suitable for outdoor use. Use copper
conductors only.
All field wiring must be done in accordance with National
Electrical Code requirements, applicable requirements of UL,
or local codes, where applicable.
Electrical wiring, disconnect means and over current
protection are to be supplied by the installer. Refer to the
rating plate for the maximum over current protection,
minimum circuit ampacity, and operating voltage. See wiring
diagram. current