Troubleshooting

If annunciator does not power on or does not appear in BBU GUI after wiring has been confirmed, use a multimeter to
check the following pins for resistance and voltage according to the below instructions.

BBU Measurements

1. Turn on the BBU.
2. Measure voltage from 1->3 and 2->3.
1 to 3
2 to 3
1. Turn off the BBU.
2.
Measure the resistance from 1->3, 2->3, and 1->2.
1 to 3
2 to 3
1 to 2

Annunciator Panel Measurements

1. Turn ON the annunciator panel.
2. Measure voltages across 1->3 and 2->3
Voltage should be around 1.65V +- 0.05V.
1 to 3
2 to 3