ABB ACH580-01 Series Quick Installation And Start-Up Manual - Page 9

Browse online or download pdf Quick Installation And Start-Up Manual for Industrial Equipment ABB ACH580-01 Series. ABB ACH580-01 Series 17 pages. Base drive replacement
Also for ABB ACH580-01 Series: Manual (16 pages), Instructions Manual (8 pages), Instructions Manual (7 pages), Quick Installation And Start-Up Manual (17 pages), Quick Installation And Start-Up Manual (17 pages)

ABB ACH580-01 Series Quick Installation And Start-Up Manual
Control cable installation examples
This section shows examples for routing the control cables in frames R4 and R6...R9. Frames R1...R3 and R5 are similar to
frame R4.
R4
EIA-485 embedded fieldbus connection
You can connect the drive to a serial communication link with a fieldbus adapter module or the embedded fieldbus
interface. The embedded fieldbus interface supports BACnet.
To configure BACnet communication with the embedded fieldbus:
1.
Connect the fieldbus cable and the required I/O signals. Use Belden 9842 or equivalent. Belden 9842 is a dual twisted,
shielded pair cable with a wave impedance of 120 Ohms.
2.
If the drive is at the end of the fieldbus, set the termination switch to ON.
3.
Power up the drive and set the required parameters. Refer to
R6...R9
Motor overload protection
.
9