Siemens SINAMICS G120 Operating Instructions Manual - Page 20

Browse online or download pdf Operating Instructions Manual for Industrial Equipment Siemens SINAMICS G120. Siemens SINAMICS G120 32 pages. Using blocksize converters in marine applications
Also for Siemens SINAMICS G120: Getting Started (46 pages), Getting Started (30 pages), Hardware Installation Instructions (2 pages), Installation Instructions And Owner's Manual (2 pages), Installation Instructions (2 pages), Installation Instructions (2 pages), Compact Operating Instructions (32 pages), Manual (42 pages), Getting Started (50 pages), Device Manual (34 pages), Quick Install Manual (2 pages), Application Description (50 pages), Compact Operating Instructions (2 pages), Manual (31 pages), Applications Manual (34 pages), Compact Operating Instructions (2 pages), Compact Operating Instructions (2 pages)

Siemens SINAMICS G120 Operating Instructions Manual
Commissioning
4.1 Commissioning with STARTER or Startdrive
Loading the configured data into the drive
Procedure with STARTER
Proceed as follows to load the configured data into the drive:
1. Select your drive.
2. Go online:
STARTER compares your configuration with the real inverter. STARTER signals any
differences in the "Online/offline comparison".
Acknowledge the message by pressing the "Load HW configuration to PG" button.
3. Open "Drive Navigator".
4. Select the "Commissioning" button.
5. Click on "Load data to the drive".
6. ☑ In the following screen form, select "After loading copy RAM to ROM".
7. Load your configuration into the inverter.
8. Wait until loading has been completed.
9. Close the "Commissioning" screen form.
You have loaded your configuration into the drive and therefore commissioned the system.
Procedure with Startdrive
Proceed as follows to load the configured data into the drive:
1. Select your drive.
2. Press the "Load to device" button.
3. ☑ In the following screen form, select "Back up parameter assignment in the EEPROM".
4. Load your configuration into the inverter.
5. Wait until loading has been completed.
You have loaded your configuration into the drive and therefore commissioned the system.
20
.
.
Compact Operating Instructions, 01/2016, A5E37058195B AA
CU250S-2 Control Units