Ook voor Apollo Smoke Detector XP95: Installatie- en onderhoudshandleiding (4 pagina's), Installatiehandleiding (2 pagina's), Installatiehandleidingen (2 pagina's), Installatiehandleiding (2 pagina's), Snelstarthandleiding (2 pagina's), Snelstarthandleiding (5 pagina's), Installatiehandleiding (2 pagina's)

Apollo Smoke Detector XP95 Installatiehandleiding
No
de
Op
64
I
OFF
ON
Tx
Plug
Tx
Tx
Rx
www.acornfiresecurity.com
Step by step guide to aligning and calibrating
1. Check that the cables at the interface (Fig 4 on page 6) are correctly con-
nected and switch the interface to alignment mode.
2. Power up the beam detector.
3. After fi tting the transmitter and receiver as described in point 3 on page
8, loosen the transmitter so that it can be moved with slight resistance up,
down, left and right.
4. Remove the plug on the transmitter.
5. Using a 0 point cross-head or terminal screwdriver turn the potentiometer
fully anti-clockwise. This adjusts the transmitter power to maximum.
6. The transmitter must be correctly targeted at the receiver by a combination
of movements, up and down, right and left until the centre of the beam hits
the centre of the receiver.