ADF 1000 NMV LINEA ZERO CLEARANCE BOX ASSEMBLY INSTRUCTIONS
Minimum Dimensions for Heat Resistant board:
300mm
above ZCB
• Non Combustible Board – Fibre Cement Sheet of 12 or 18mm thick to
prevent cracking, or Skamol Board 40mm or 50mm thick.
• Fix with separate sheets top and bottom, and separate off cuts on each
side. Use the factory cut neat edge to face the heater opening, if not
covering with optional frame or tiling. This is so plastic (will melt) or metal
(will expand and contract) beading is not to be used on the heater opening.
Must leave a 5mm gap between each edge of the heater and the combustible
board to allow for metal expansion.
1445mm to 45mm stud centres.
1355mm opening
1/11/19
1420mm