7. Configuration of AVM 1002D

The front panel of the AVM 1002D module contains three buttons, labeled subsequently UP,
DN and SET. These buttons are used to edit the module functions.
7.1

Entering the menu

During normal operation of the AVM 1002D module, pressing UP or DN button will cause
entering into the device menu, which is indicated by rapid blinking of the OK LED.
While in edit mode, buttons UP/DN scroll the menu items:
A – alarm,
U – warning,
d – thresholds activation delay,
L –
latching
of alarm threshold or warning threshold
CA – alarm activation in case of the sensor circuit failure,
CU – warning activation in case of the sensor circuit failure,
SC – correction of values indicated by the module,
Er – indication of sensor failure,
AU – selection of vibration signal estimate.
7.2

Setting up of the alarm threshold 'A'

The AVM 1002D has the ability to activate the built-in relay, when the signal from the vibration sensor
exceeds the threshold value.
To set the alarm threshold one should perform the following procedure:
1. Press UP/DN. Afterwards the OK LED will blink rapidly, which indicates entering into the
device menu.
2. By pressing UP/DN set the letter 'A' on the display.
3. Confirm by pressing the SET button.
4. Use the UP/DN buttons to select the desired alarm threshold value in the range from 0.0 to
99. Alarm threshold value cannot be lower than the warning threshold value.
5. To confirm the change, press the SET button.
If the vibration sensor signal will exceed the alarm threshold value and will remain above it for the time
the configured delay, the alarm relay will be activated.
To disable the alarm threshold, instead of the numerical value from the range from 0.0 to 99, set the
'FF' value on the display and confirm by pressing the SET button.