Starting 1" (25 mm) past the Scotch
half-lapped layers of 3M
temporarily secure the ends of the 31 tape acket until the jacket reaches full bond.
1"
(25 mm)
5.0
Repairing Damaged Cable Jacket
Note: For jacket repair option, additional tape may be needed for longer repairs.
5.1
Remove damaged cable jacket and taper jacket approximately 1" (25 mm).
5.2
Scuff and clean 3" (75 mm) of cable jacket beyond each split end.
Scuff &
Clean
3"
(75 mm)
5.3
Start 1" (25 mm) above split or top of taper and apply half-lapped layers of
Scotch
Linerless Rubber Splicing Tape 130C (tacky side DOWN) to 1"
®
(25 mm) past end of opposite split or top of taper. Apply half-lapped layers,
filling all voids until the area is returned to greater than or equal to original
cable profile.
Temflex
™
3M
Temflex
™
1"
(25 mm)
1" (25 mm)
past split or
top of taper
Heavy Duty Mining Tape 31, apply 3
®
Vinyl Electrical Tape 1700P to each end to
™
Vinyl Electrical Tape 1700P
™
Figure 11
1"
(25 mm)
Figure 12
Scotch
Linerless
®
Rubber Splicing Tape 130C
Tacky Side DOWN
Figure 13
6
1"
(25 mm)
Scuff &
Clean
3"
(75 mm)
1" (25 mm)
past split or
top of taper
78-8127-6830-3-C