Prepare Cable
6.1
Position cable ends so that conductor color rotation matches.
6.2
Circle-cut cable jacket approximately 12" (305 mm) from each end. Be sure not
to damage cable conductors.
6.3
Measure approximately 14" (355 mm) from cable end and fully taper cable
jacket down to circle cut.
4"
(100 mm)
Scuff & Clean
Circle cut cable jacket
6.4
Remove approximately 12" (305 mm) of cable jacket.
6.5
Scuff and clean 4" (100 mm) of cable jacket beyond each split end.
6.6
Remove cable fillers.
Instructions for Round Cables