Autonics ARD-AI04 Podręcznik - Strona 5

Przeglądaj online lub pobierz pdf Podręcznik dla Systemy wejścia/wyjścia Autonics ARD-AI04. Autonics ARD-AI04 10 stron. Devicenet remote i/o analog, terminal block type
Również dla Autonics ARD-AI04: Instrukcja obsługi produktu (4 strony)

ARD-A Series

I/O Circuit Diagram

Type
DeviceNet connector
CAN_H
SHIELD
CAN_L
Analog
input
CAN_H
SHIELD
CAN_L
Analog
output
Connections
※ When wiring the communication connector, use cable and tap which meet the DeviceNet standard
and tighten the connector screw with a tightening torque of 0.5N . m.
※ When wiring the input/output terminal, tighten the connector screw with a tightening torque of 0.5N . m.
lARD-AI04
※1
Short
V
I
V
I
V
0+
0+
1+
1+
2+
V
AG
V
AG
V
0-
1-
2-
V
mA
※ 1: For current input, short between V

Terminating Resistance

● 120Ω
● 1% of metallic film
※ D o not install terminating resistance on ARD unit or it may cause network problem (impedance can be too high or low)
or malfunction.
Connect terminating resistance on the both ends of the trunk line.

Communication Distance

Baud Rate
125kbps
250kbps
500kbps
X-28
V+
Inner circuit
V-
Power circuit
V+
Inner circuit
V-
Power circuit
N . C
N . C
I
V
I
2+
3+
3+
N . C
N . C
AG
V
AG
3-
and I
.
□+
□+
● 1/4W
Max. length of
Max. network length
branch line
500m
6m
250m
6m
100m
6m
Inner circuit
Input circuit
Power circuit
Analog
GND
Output circuit
Power circuit
lARD-AO04
N . C
N . C
V
V
I
I
0+
1+
0+
1+
N . C
COM
COM
COM
COM
V
mA
Allowable expansion
length of branch line
156m
78m
39m
External connections
V
0+
I
0+
V
0-
V
1+
I
1+
V
1-
AG
V.OUT
Load
Max. 1KΩ
COM
I.OUT
Load
COM
Max. 600Ω
Analog
GND
N . C
N . C
N . C
N . C
N . C
N . C
N . C
N . C
N . C
V
mA
0-5VDC
1 to 5VDC
Voltage
-5-5VDC
0-10VDC
-10-10VDC
DC0-20mA
Current
DC4-20mA