Akw M11 DigiPump Instruções de instalação e cuidados do utilizador - Página 4
Procurar online ou descarregar pdf Instruções de instalação e cuidados do utilizador para Produto de canalização Akw M11 DigiPump. Akw M11 DigiPump 20 páginas.
Mechanical And Plumbing Installation
Positioning
The AKW M11 DigiPump shower waste water pump must be installed by a
suitably qualified, competent person eg. NIC EIC, in accordance with current IEE
Wiring Regulations (BS7671), building regulations and local by-laws.
This product is rated at IP45 and suitable to be installed in Zone 1 or Zone 2
of a shower room only if these instructions are fully complied with.
The unit must be located away from the direct line of water jets.
Note: Zone 1 lies above zone 0 and below 2250mm (88in) vertically above a shower
tray or wet floor area.
The perimeter of zone 1 of a wet floor is within a 1.2 metres (47in) radius of the
shower head position. Consult BS7671 for further clarification.
FOR GUIDANCE ONLY- PLEASE REFER TO BS7671 FOR FURTHER DETAILS
4
© 2012 AKW Limited