AmpleNess S52100G Manual do utilizador - Página 11

Procurar online ou descarregar pdf Manual do utilizador para Acessórios para câmaras AmpleNess S52100G. AmpleNess S52100G 20 páginas. Storage lithium battery

5. Installation

5.1 Installation Location
Make sure that the installation location meets the following conditions:
The building is designed to withstand earthquakes, and the floor is flat and level.
Far away from the sea to avoid salt water and humidity.
The installed location should not be access by pet and children.
No flammable or explosive materials nearby, at least 2.5m far away from combustible.
Minimal dust and dirt in the area.
No corrosive gases present, including ammonia and acid vapor.
The battery optimal operate temperature is 15°C to 30°C. Frequent exposure to severe
operating condition would exacerbate the performance and lifetime of the battery.
5.2 Installation Requirements
The installation shall be in a restricted access location/ room or in a cabinet where provides a
barriers for the battery terminal.
The maximum number of battery shall be not over 16 PCS.
5.3 Installation Materials
Following installation materials should be prepared by installers.
Power cable
Data cable
Earth cable
Ground wire
Bipolar external isolator, when two or more battery systems in parallel, each of them shall
have a bipolar isolator. Meanwhile, the isolator shall have ability to break the full load
current.
NOTICE
Make sure that the cross-sectional area of charging cables is 25 to 35 mm
NOTICE
A breaker between battery and inverter was recommended to install, and the
breaker's min. current should be over 150 A or following with local regulations.
AMPLENESS Lithium Battery S52100G User Manual
9
2
.