Dell PowerEdge 6800 Manual de resolução de problemas - Página 15

Procurar online ou descarregar pdf Manual de resolução de problemas para Servidor Dell PowerEdge 6800. Dell PowerEdge 6800 16 páginas. Installation and troubleshooting guide (.htm)

Removing the Trim Panel

1 Lay the system on its cover as shown in Figure 1-7.
Figure 1-7. Removing the Trim Panel
hex-head Phillips screws (6)
2 Using a #2 Phillips screwdriver or 1/4-inch nut driver, remove the three screws from the side
of the trim panel. See Figure 1-7.
3 Using a #2 Phillips screwdriver or 1/4-inch nut driver, remove the three screws from the back
of the system.
4 Slide the trim panel backward and then remove the trim panel from the chassis.
5 If not already present on the system, install the six shoulder screws included with the kit,
attaching three screws to each side. See Figure 1-7.
NOTE:
The shoulder screws must be tightened firmly enough (10.8 to 13.2 in-lbs of torque) to
support the weight of the system in the rack and to prevent loosening.
The system is ready to install in the rack.
shoulder mounting
screws (6)
Tower-to-Rack Conversion Guide
15