Cisco ONS 15454 Instalar - Página 15
Procurar online ou descarregar pdf Instalar para Servidor Cisco ONS 15454. Cisco ONS 15454 32 páginas. Four-shelf and zero-shelf bay assembly
Também para Cisco ONS 15454: Manual de instruções de instalação (22 páginas), Instalar (32 páginas), Desembalagem e instalação (42 páginas), Desembalagem e instalação (40 páginas)
Chapter 1 Install the Shelf and Backplane Cable
Figure 1-3
Insert and tighten three screws to secure the AEP to the backplane.
Step 4
Connect the AEP cable to the backplane and AEP:
Step 5
Connect the 10 colored wires to the wire-wrap pins on the backplane.
a.
cable wires are connected.
Plug the other end of the AEP cable into AEP connector port. The brown pin is on the top.
b.
Figure 1-4
78-18537-01
Installing Standoffs and the AEP
Wires
AEP cable
Connector
Table 1-1
AEP Wire-Wrap Connections to Backplane Pins
NTP- A119 Install the Alarm Expansion Panel
shows AEP and AIC-I signals that each wire carries.
Cisco ONS 15454 Procedure Guide, Release 8.5.1
Figure 1-4
shows where the
1-15