Aleko AC 1500 Manual do utilizador - Página 13

Procurar online ou descarregar pdf Manual do utilizador para Abertura de portões Aleko AC 1500. Aleko AC 1500 16 páginas. Sliding

Aleko AC 1500 Manual do utilizador
DIP Switch #1– #2: Running time of the motor in Midway Mode
DIP Switch #1: ON –2 Seconds OFF –0
DIP Switch #2: ON –4 Seconds OFF –0
NOTE: The midway mode function would be disabled if both DIP switches are turned off. Factory
default setting is disabled.
E.g.
Running time of the operator in pedestrian mode is 2 seconds.
DIP Switch #3: Auto close function enabled/disabled
DIP Switch #3: ON –auto close function enabled
OFF –auto close function disabled
E.g.
Auto close function of the opener has been enabled. Factory default setting is disabled.
DIP Switch #4: Left/Right open
2. Potentiometers
Potentiometer A and B are used to adjust the stall force and auto close time of the gate operator separately.
Turn potentiometer A clockwise to increase the stall force, and turn it counter-clockwise to decrease the
stall force.
Turn potentiometer B clockwise to increase the auto close time, and turn it counter-clockwise to decrease
the auto close time, the auto close time could be adjusted steplessly from 1 to 99 seconds.
12