AGS Parksafe Control Panel Руководство по установке и эксплуатации
Installation & Operation Manual

INSTALLATION

Planning

The Parksafe control panel is designed for installation into car parking facilities and enclosed
garages. It is designed to be paired with AGS Parksafe Gas Detectors (Nitrogen Dioxide and
Carbon Monoxide) that will be linked via MODBUS back to the control panel and monitor the
connected detectors in numbers up to 16 (per control panel) and automatically control ventilation
systems according to gas levels and an optional temperature level.
The Parksafe will make or break a dry contact internally on OUTPUT 1 and a second contact on
OUTPUT 2. This is to have a live feed to the ventilation system wired through the contact so that the
Parksafe can activate ventilation/ fans, this can either be via a direct live feed or via a run signal.
There is another output relay that will activate after OUTPUT 2 has been activated for an optional
extended period of time. This can be used for a link to the BMS or other external indication device.
The Parksafe also has a 0-10VDC output to allow the panel to drive VSD's based on gas level
outputs. The Parksafe control panel is designed to be located in an office or other suitable area
within a carpark not accessible to the public.
Please refer to your detector manual for important information regarding coverage, location and
positioning including areas and conditions to avoid!

Typical Installation Arrangement

Place the control panel in accordance with regulations ensuring optimum access and monitoring.
The control panel should be located outside of the hazardous area that it is monitoring.
Easy accessibility is required both for status observation and alarm purposes.
Where connections may exceed 500 yards from one control panel – Contact your supplier!
The use of sound strobes are highly recommended!
AGS Parksafe Panel - IOM Iss: 6 10-20