operation manual
MPPT solar charge controller X45/10
12. Security Features
mistake
short circuit
overcurrent
countercurrent
Overvoltage Max. 45V
undervoltage
Overtemperature The controller cuts off the load when the temperature reaches the set value.
*1 Controller can protect itself, but the load might be damaged.
*2 The battery must be protected by a fuse.
ATTENTION:
The combination of different error states can lead to damage to the controller. Always
troubleshoot first before reconnecting the controller.
13. Specifications
a-TronlX MPPT solar charge controller X45/10
battery parameters
Max charge current
Mains voltage
Max. voltage at battery terminal Battery
type
MPPT charge voltage
Voltage boost
Equalize voltage
Wet,
Float Voltage Low.
gel
Disconnect Power on again
and
AGM
Temperature compensation
02/2022
status
Protected *1
Protected
–
Protected
–
cause
remedy
Protected
Protected *1
Protected *2
Turns off immediately
–
Switches off with a delay
–
Max. 25V
–
Switch off
10A
12V
25V
Lithium, Wet, Gel, AGM (Default: Gel)
<14.5V 25
14.0-14.8V (programmable, default: 14.5V@25°C)
14.0-14.8V (programmable, default: 14.8V@25°C)
13.0-14.5V (programmable, default: 13.7V@25°C)
10.8-11.8V, SOC1-5 (programmable, default: 12V)
11.4~12.8V (programmable, default: 12V)
15.5V
-4.17mV/K per cell (boost, equalization), -3.33mV/
K per cell (float)
–
–
Item No. 9887579