8. CONTROL UNIT CONFIGURATIONS
8.1 DIP SWITCH FUNCTIONS
DIP 1
OFF - DEAD MAN OPEN
ON - IMPULSE OPEN
DIP 2
OFF - DEAD MAN CLOSE
ON - IMPULSE CLOSE
DIP 3
OFF - ELECTRONICALLY CONTROLLED
ON - INFINITE WORKING TIME
DIP 4
OFF - OPEN FUNCTION
(for three buttons transmitter, TECH3 PLUS)
ON - GO FUNCTION
(for two buttons transmitter, B.RO2WN)
DIP 5
ON - PHOTO TEST ON
OFF - PHOTO TEST OFF
DIP 6
ON - SAFETY EDGE INSTALLED
OFF - SAFETY EDGE UNUSED
8.2 WORKING TIME
BAXS900 has as an integrated function the automatic detection of working time by monitoring the motor current.
- By setting DIP 3 to OFF, the control unit interrupts the power supply to the engine when it does not detect current due to the inter-
vention of the internal limit switches inside the engine, placing itself in OPEN or CLOSED state according to the last movement.
- By setting DIP 3 to ON, the power plant continues to power the engine even when automation physically reaches opening and
closing. The power supply is interrupted only with a stop command.
ATTENTION! In this mode it is possible the unintentional opening of the automation due to the intervention of the photocells or
safety coast with the automation in closed position.
8.3 PHOTOCELLS
Connect contact Rx (receiver) photocell to contact NC input PHOTO. The interruption of the beam during the closing causes the
complete and immediate reopening of the automation. If at least one of the two DIP-SWITCHES (1 or 2) is in the OFF position, the
reopening will be partial (2 seconds of work).
8.4 PHOTOCELLS TEST
BAXS900 has the photocell test function, the test (if active) is performed before each closing movement. To enable the test, with the
photocells present, place DIP 5 in position ON and connect the photocell feed as shown in Fig. 11.
1 2 3 4
OPEN CLOSE
6-1622623 rev. 3
+
-
5 6 7 8
STOP
COM
PHOTO
TEST
- Opening only while holding the button (radio or panel)
- Opening with single pulse of the open button (radio or panel)
- Closing only while holding the button (radio or panel)
- Closing with single pulse of the open button (radio or panel)
- Working time detected and limited by the control unit
- Move the motor in open or close direction until it receive a stop
command.
WARNING! Don't set ON when using UPS
- 1st OPEN (and interrupts closing)
- 2nd STOP
- 3rd CLOSE (and interrupts opening)
- 1st GO (OPEN and CLOSE in sequence)
- 2nd STOP
- PHOTOCELLS TEST ON (functional test of photocells before every
move; see fig.11 to connection diagram.
- PHOTOCELLS TEST OFF
- Obstacle on detected edge (wireless system T.CO.O - R.CO.O or
optional board for resistive edge required, see pag. 3)
- Safety Edge not installed
Rx
Tx
PHOTO
PHOTO
COM
N.C.
+ -
+ -
Fig. 11