DSPM UniMeasure HX-VP510 Series Kurulum Kılavuzu - Sayfa 2

Dönüştürücü DSPM UniMeasure HX-VP510 Series için çevrimiçi göz atın veya pdf Kurulum Kılavuzu indirin. DSPM UniMeasure HX-VP510 Series 3 sayfaları.

HX-VP510 Series Installation Guide
Model HX-VP510
Velocity
The tachometer is self en er giz ing and requires no input voltage.
Excitation Voltage ..........4.9 to 30 VDC
Excitation Current ..........40 mA max.
Output Impedance .........10 Ω max.
Output Load...................5KΩ min.
RANGE
Note: Di men sions in
2", 10"
brackets are mil li me ters.
3", 15", 30"
4", 20", 40"
5", 25", 50"
60"
80"
Alternate Wire Rope Exit
E1
Via Paolo Uccello 4 - 20148 Milano
Tel +39 02 48 009 757 Fax +39 02 48 002 070
Wiring and Circuit Diagram
Dimensional Information
NOTE
Mount with Ø.25 or M6
Socket Head Cap Screws.
Alternate Wire Rope Exit
"A"
"B"
"C"
1.12 (28.4)
1.79 (45.5)
1.21 (30.7)
.96(24.4)
1.95 (49.5)
1.37 (34.8)
.80 (20.3)
2.11 (53.6)
1.53 (38.9)
.64 (16.3)
2.27 (57.7)
1.69 (42.9)
.49 (12.4)
2.42 (61.5)
1.84 (46.7)
.25 (6.4)
2.66 (67.6)
2.08 (52.8)
E2
E3
As shown in the diagram above, both commons on pins "B" and "C"
are con nect ed to geth er in ter nal ly at the transducer, so that either a
3-wire or 4-wire con nec tion to the trans duc er may be made.
With small blade type screwdriver (.105" max. blade width X .023"
max. blade thickness), adjust the Zero and Span controls on the
trans duc er to set zero output voltage and max i mum output volt-
age. Note: The Zero and Span con trols are some what interactive
and may require sev er al it er a tions to ob tain the desired zero and
maximum settings.
Extend the cable (on angular position transducers, ro tate shaft) of
the trans duc er to the de sired zero position (must be within 0% to
30% of range.) Adjust the Zero control so that the output voltage
is zero. Then extend the cable (on angular position transducers,
ro tate shaft) to the desired max i mum position (must be within 80%
to 100% of range.) Adjust the Span control for max i mum output
voltage required (unit will adjust from 5 VDC to 10 VDC). Re check
the zero set ting and ad just if nec es sary. Recheck the Span set ting
and re ad just if nec es sary.
NOTE
Mount with Ø.50 or M12 Socket Head Cap Screws.
Alternate Wire Rope Exit
[email protected] www.dspmindustria.it