Ayrıca Jandy Jandy Pro Series için: Kullanıcı El Kitabı (12 sayfalar), Kurulum Kılavuzu (16 sayfalar), Kurulum ve Kullanım Kılavuzu (20 sayfalar), Manuel (8 sayfalar), Hızlı Başlangıç Kılavuzu (2 sayfalar), Kurulum ve Kullanım Kılavuzu (20 sayfalar), Kurulum Talimatları (2 sayfalar), Kurulum ve Kullanım Kılavuzu (16 sayfalar), Kurulum ve Kullanım Kılavuzu (16 sayfalar), Kurulum ve Kullanım Kılavuzu (16 sayfalar)

Jandy Jandy Pro Series Kullanıcı El Kitabı
Page 6
3.
A standard 1.5" plastic wall / return fi tting (not included) must be
installed so that the top edge of the underwater light's lens is at least 4
inches (10.2 cm) below the surface of the water in the pool.
See Figure 1.
NOTE: For optimal lighting results it is recommended to place lights 12-18"
below the water line.
NOTE: To be certain that the pool's electrical system meets all applicable
requirements, the electrician should also consult the local building
department.
12 VAC Class 2 Magnetic
Transformer or
Junction Box
Rigid 1" electrical conduit. Sweep
elbows only, no 90º elbows.
NOTE: Verticle installations such as bench and walk-out locations will use ALL of the same clearance requirements.
The light face must be completely snug with the light fitting without any protrusion from the light fixture.
Figure 1.
Jandy
Plastic Fitting
Use the chart below to determine the appropriate pipe length for your
installation.
WATTS
6W
12W
24W
All products listed above come in a variety of cord lengths. Cord lengths
Table 1.
Jandy
ENGLISH
48" min.
Check AHJ for other J-box requirements
Pro Series LED Light Installation with Standard 1.5"
®
MINIMUM LENGTH FOR 1.5" PIPE
come in 50, 100 & 150 feet lengths.
Pro Series LED Light Minimum 1.5" pipe length
®
Nicheless Underwater LED Lights | Owner's Manual
8" minimum to maximum water level
Maximum possible water line.
(top of copping)
4" minimum to top of lens
1.5" pipe. Length requirement varies
by model. (See Table 1)
7"
10"
10"