Chapter 4
Maintenance and Upgrade Procedures
Connecting DC Power to the ASA 5585-X
This section describes how to connect DC power to the Cisco ASA 5585-X, and contains the
following topics:
•
•
Prerequisites
Before you connect the power supply module to a power source, be sure the chassis is properly grounded.
Caution
Use the following tools and parts to connect the DC power-supply module:
•
•
•
•
Table 4-5
Table 4-5
Lug
Source DC cable lugs
Source DC ground cable lugs
Before performing any of the following procedures, ensure that power is removed from the DC circuit.
Warning
Statement 1003.
OL-22567-02
Prerequisites, page 4-19
Connecting the DC Power Supply, page 4-20
5/16-inch nut-driver
M4 nut-driver
Source DC cable lugs with the following requirements:
–
Two holes with 0.62±0.02-inch spacing between the hole centers to accommodate the
power-supply terminal posts.
A 90-degree bend in the barrel to allow the source DC cables to exit the terminal block.
–
Source DC ground wire lugs with the following requirements:
•
A single hole that can accommodate the 4-mm ground post.
•
Either a straight or bent barrel.
The source DC cable and the terminal block lugs should be sized according to local and
Note
national installation requirements and electrical codes. Use only copper wire. We
recommend FCI Burndy type YA4CL-2TC10-90 and Panduit type LCD10-10AF-L
dual-hole 90 degree lugs, or the equivalent.
These parts and tools are not supplied as part of the chassis accessory kit or the DC
Note
power-supply module kit. You must purchase them separately.
shows the source DC cable and ground cable-lug tightening torque ratings.
Lug Torque Ratings
Maximum Torque
4.07Nm
2.5Nm
Cisco ASA 5585-X Adaptive Security Appliance Hardware Installation Guide
Removing and Installing the Power Supply Module
Recommended Torque
2.5Nm
2Nm
4-19