Cisco UCS B200 M4 Servis Kılavuzu - Sayfa 10

Sunucu Cisco UCS B200 M4 için çevrimiçi göz atın veya pdf Servis Kılavuzu indirin. Cisco UCS B200 M4 24 sayfaları. For e5-2600 v4 series cpus
Ayrıca Cisco UCS B200 M4 için: Kurulum ve Servis Notu (30 sayfalar), Kurulum ve Servis Notu (46 sayfalar), Yükseltme Kılavuzu (9 sayfalar)

Cisco UCS B200 M4 Servis Kılavuzu

Removing a Heat Sink and CPU

Do one of the following actions:
• If the server software and firmware are already at the required minimum version as shown in the preceding
• If the server software or firmware is not at the required minimum version, follow the instructions in the
Removing a Heat Sink and CPU
Procedure
Step 1
Unscrew the four captive screws.
Step 2
Remove the heat sink.
Figure 7: Removing the Heat Sink and CPU
Step 3
Unhook the self-loading socket (SLS) lever that has the unlock icon
Step 4
Unhook the SLS lever that has the lock icon .
Step 5
Grasp the sides of the CPU carrier (indicated by the arrows in the illustration) and swing it into a standing
position in the SLS plug seat.
Servicing a Blade Server
10
table, replace the CPUs by using the procedure in the following section.
Cisco UCS B200 M4 Server Upgrade Guide for E5-2600 v4 Series CPUs
the CPUs by using the procedure in the following section.
Servicing a Blade Server
to upgrade it. Then replace
.