Removing a Heat Sink and CPU
Do one of the following actions:
• If the server software and firmware are already at the required minimum version as shown in the preceding
• If the server software or firmware is not at the required minimum version, follow the instructions in the
Removing a Heat Sink and CPU
Procedure
Step 1
Unscrew the four captive screws.
Step 2
Remove the heat sink.
Figure 7: Removing the Heat Sink and CPU
Step 3
Unhook the self-loading socket (SLS) lever that has the unlock icon
Step 4
Unhook the SLS lever that has the lock icon .
Step 5
Grasp the sides of the CPU carrier (indicated by the arrows in the illustration) and swing it into a standing
position in the SLS plug seat.