Single Point Mode: 2-Point Teach (Only O200.G, O200.R)

5.2.2
Defines SP1 based on TP1 and TP2 for an optimized switching behaviour.
O200.G:
Teaches the position of the object and of the background.
O200.R:
Teaches the sensor hitting the reflector with and without an object in between
Command sequence:
Place object at desired switching distance
-
Execute Teach SP1 TP1 to teach TP1
-
Execute Teach SP2 TP2 to teach TP2
-
Execute Teach Apply to store the setpoint
-
O200.G:
SP1 = (TP1 + TP2) / 2
O200.R:
SP1 = sqrt(TP1 * TP2)

Window Mode: Window Teach (Only O200.G)

5.2.3
If the selected SSC is configured to Window mode (Section 4.3.2.1), following command sequence can be
applied to teach-in SP1 and SP2:
Command sequence:
Place object at desired switching distance
-
Execute Teach SP1 to teach-in the distance related to SP1
-
Execute Teach SP2 to teach-in the distance related to SP2
-
Execute Teach Apply to store the setpoint
-
By executing Teach Cancel the teach-in procedure can be canceled at any state as long Teach Apply has not
been used before.
Which SP was teached at a higher distance does not have any influence on the switching behavior
(SP1<SP2, SP1>SP2).