5.3 Dynamic (Only O200.G, O200.R)

By using the dynamic teach-in commands, it is possible to define the setpoints by evaluating the minimum
and maximum measurement values within a time frame.Accepted duration: 2 ... 15 sec.
When to apply?
For moving and/or small objects
-
The command sequence to perform a dynamic teach-in is the same for all switching modes.
Command sequence:
Execute DynamicTeach Start to start the data acquisition
-
Execute Dynamic Teach Stop to stop the data acquisition
-
Execute Teach Apply to store the setpoint
-
By executing Teach Cancel the teach-in procedure can be canceled at any state as long Teach Apply has not
been used.
Parameter name
Dynamic Teach SP Start
Dynamic Teach SP Stop
Teach Apply
Teach Cancel

Dynamic in Single Point Mode

5.3.1
If the selected SSC is configured to Single Point mode (Section 4.3.2.1), during the dynamic teach-in the
minimum and maximum values are evaluated and the setpoint SP1 set to the middle
O200.G:
SP1 = (Min + Max) / 2
O200.R:
SP1 = sqrt(Min * Max)
en_BA_O200_IO-Link_V1.docx
15.08.2018/
Short Description
Starts the data acquisition.
Stops the data acquisition
Figure 28: Dynamic Single Point Teach, switching behavior
31/34