4.2 CABLE SELECTION AND WIRING
The transmitter output (–, S, +) terminal block connects to the (–, S, +) connections on a
channel terminal block of the monitor (one transmitter per channel), as shown in FIGURE 4.
Connection should be made using 3-conductor, shielded cable (shield must be grounded at the
monitor). Run cable through steel conduit for best signal transmission and maximum allowable
distances.
The maximum permissible distance between the transmitter and monitor is
dependant on wire gauge as shown in the following Cable Selection Chart (FIGURE 3)
FIGURE 3: Cable Selection Chart.