ESI ESRTP4+ Manual de instrucciones de instalación - Página 7
Navegue en línea o descargue pdf Manual de instrucciones de instalación para Termostato ESI ESRTP4+. ESI ESRTP4+ 11 páginas. Programmable room thermostat
También para ESI ESRTP4+: Instrucciones de uso (11 páginas)
- 1. Table of Contents
- 1. 1 Technical Specification
- 1. Programmable Room Thermostat
- 2. 2 Installation Instructions
- 2. Installation Safety Instructions
- 2. General Safety
- 2. Maintenance
- 2. Wiring Diagram
- 3. 3 Technical Settings
- 3. Setting TPI, Delayed & Optimum Start
- 3. Setting Sensitivity/Swing and Calibration
- 3. Opentherm Parameter Settings
- 3. Setting the Landlord Service & Time Events
- 3. Lockout Feature
the Next
button and the technical settings menu will
be displayed. Release all buttons.
2. Press the Next
button until you get to the SWING
settings (5U1n9 is displayed at the bottom of the LCD
next to a flashing 0.5). Press +/– to choose between 0.5
to 2.0
3. Press the Next
button to enter the ADJ settings.
Press +/– to choose between -3 to 3 (this calibrates the
temperature).
Opentherm Parameter Settings
3.3
OpenTherm Settings:
°C
AUTO DS OS SER OST TPI MAN
To Adjust the Opentherm Settings:
1. Move the slider to the OFF position
2. Press and hold A, H and the
Parameter 01 on the right-hand side of the screen is
°C
displayed.
3. Continue to press the Next
AUTO DS OS SER OST TPI MAN
the different menus below
12
AM
PM
SET
A
C
H
Home button until
AM
PM
button to scroll through
SET
Menu Parameter Settings
Parameter Feature
01
Low Load control
02
Flow Water Temperature
03
Return Water Temperature
04
Domestic Hot Water
Temperature
05
DHW settings
06
Hot Water Set Point
Setting the Landlord Service & Time Events
3.4
1. Switch the slider to OFF. Press and keep holding the A
and H buttons together (under the fascia), now press
the Next
button and the technical settings menu will
be displayed. Release all buttons.
2. Press the Next
button until you get to CODE. A
numeric password will be required to enter this section.
The factory default password is 0000.
N.B. The screen will display Err if the incorrect password is
entered.
3. Press +/– to enter the first digit of the password. Press
the H button to move to the next digit. Repeat this until
all 4 digits have been entered.
4. Press the Next
button to enter the service interval
settings.
5. Use the +/– buttons to choose between:-
OFF: Turns the service interval off
Comment
Use + or – to disable (OFF) /
enable (ON). default is ON.
Use + or – to disable (OFF) /
enable (ON). default is OFF
(60°c default setpoint) N.B. Hot
Water Set Point is only displayed
if DHW is enabled in 05 above
13