Siemens SIPART PS2 Instructions d'installation - Page 6

Parcourez en ligne ou téléchargez le pdf Instructions d'installation pour {nom_de_la_catégorie} Siemens SIPART PS2. Siemens SIPART PS2 11 pages. Mounting bracket kit
Également pour Siemens SIPART PS2 : Instructions d'installation (4 pages), Manuel d'utilisation (28 pages), Instructions d'installation (4 pages), Manuel d'installation du matériel (30 pages), Description technique (26 pages), Mode d'emploi Compact (35 pages), Instructions d'installation du kit (9 pages)

Siemens SIPART PS2 Instructions d'installation
15900-795
Install Mounting Plate and PS2 Assembly onto Actuator
1. Install 5/16" lock washers onto 5/16-18x0.75 Hex head bolts
2. Since mounting plate is intended for several actuator models, be sure fasteners are inserted
through proper slots and/or holes. Proper slots/holes are shaded in table 3 below.
Actuator
Model
Number
M-00
M-11
M-33
M-22
3. Using the two 5/16" hex head bolts, secure mounting plate assembly onto the two actuator
threaded holes. Table 4 illustrates location of bolts within slot so feedback arm is perpendicular to
actuator/valve stem at 50% of travel.
IMPORTANT: Be sure feedback pin engages spring clip and arm slot while making this assembly.
Proper Bracket
Holes/Slots
Shaded Area
TABLE 3, Proper Mounting Holes/Slots
Actuator Model
Number
M-44-78
M-44-108
6
Proper Bracket
Holes/Slots
Shaded Area