1. Select parameter 620 Operation Mode
2. Select data value [3] (Initialize)
3. Cut mains
The frequency converter has now been programmed
for factory setting. The following parameters are not
reset during manual initialisation:
- Par. 600 Operating hours
- Par. 601 Hours run
- Par. 602 kWh counter
- Par. 603 Number of power-ups
- Par. 604 Number of overtemperatures
- Par. 605 Number of overvoltages
■ Future Ordering
For future ordering it is necessary to state the order
number for the power unit as well as the control unit.
The power unit order number is placed on top of the
power unit, whereas the control unit order number is
placed on the back of the front cover