DVC 5370 설치, 운영 및 유지보수 매뉴얼 - 페이지 12
{카테고리_이름} DVC 5370에 대한 설치, 운영 및 유지보수 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. DVC 5370 16 페이지. Mechanical limit switch with valve and led
4. 6. Circuit connection
Main voltage
Type 5370 controller could be connected with different voltage:
Power: DC24 V(standard)
AC 110V,220V (optional)
Electronic component
All of the electronic components in the control device of Type 5370 are equipped with built-in pin connectors
which avoid unnecessary wiring and interference. According to standard, a PCB could be connected with 3
solenoid valves (V1, V2, V3) at most and with 4 output of position feedback.
Default setting as follows:
Output:
156123-Displacement version
S1,S2
Output DC24V+ (standard configuration)
A +
Analog signal output 4-20mA positive electrode +
A -
Analog signal output 4-20mA negative electrode -
156133 -AS-I Bus protocol version
S1,S2, Output DC24V+ (standard configuration)
AS-INTERFACE BUS protocol communication
Input:
Signal input 24V+, control panel or PLC
V1 - the 1st solenoid valve (driving by single-acting)
Signal light:
S1 - turning on the detecting
position of valve (Green LED light)
S2 - turning off the detecting
position of valve (red LED light)
11 / 15