NTP- A6 Install the Power and Ground
Connect the unit only to DC power source that complies with the safety extra-low voltage (SELV)
Warning
requirements in IEC 60950 based safety standards. Statement 1033
This product requires short-circuit (overcurrent) protection, to be provided as part of the building
Warning
installation. Install only in accordance with national and local wiring regulations. Statement 1045
A readily accessible two-poled disconnect device must be incorporated in the fixed wiring.
Warning
Statement 1022
Warning
This unit might have more than one power supply connection. All connections must be removed to
de-energize the unit. Statement 1028
Always use the supplied ESD wristband when working with a powered ONS 15454. Plug the wristband
Caution
cable into the ESD jack located on the lower-right outside edge of the shelf assembly.
Verify one of the following:
Step 1
If you have the 15454-SA-ANSI or 15454-SA-HD shelf, a 100-A fuse panel (35-A fuse per shelf
minimum) should be installed. If not, install one according to manufacturer's instructions.
If you have the 15454-SA-NEBS3 shelf, a standard 80-A fuse panel (20-A fuse per shelf minimum)
should be installed. If not, install one according to manufacturer's instructions.
Complete the
Step 2
Complete the
Step 3
Complete the
Step 4
Continue with the
Step 5
Stop. You have completed this procedure.
Cisco ONS 15454 Procedure Guide, Release 8.5.1
1-10
"DLP-A16 Connect the Office Ground to the ONS 15454" task on page
"DLP-A17 Connect Office Power to the ONS 15454 Shelf" task on page
"DLP-A18 Turn On and Verify Office Power" task on page
"NTP-A7 Install the Fan-Tray Assembly" procedure on page
Chapter 1 Install the Shelf and Backplane Cable
17-18.
17-19.
17-22.
1-11.
78-18537-01