Rated insulation voltage
Insulation class in acc. to UL1022
Dielectric voltage-withstand test
Rated service rating
Rated mains voltage of VN
Frequency range of VN
Operating range of VN
Max. power consumption
Measuring current
Monitor hazard current 120V / 208V (1Ph) / 208V (3Ph) max. 35 /
62 / 68 µA
Min. internal impedance at 1Ph / 3Ph (60 Hz) 3.5 / 3.2 MΩ
Nominal response value
Response tolerance
Response retardation
Response hysteresis
Output contact assemblies one voltage-free SPDT and one 12 V
DC, 200mA contact
Rated contact voltage
Make capacity
Break capacity at 24 V DC and L/R = 0
Switching life (220 V AC / 60 Hz)
Operation mode
LIM overload protection built-in thermal overload with automatic
reset
Ambient temperature when operating 10
Ambient temperature when stored -20
Mounting orientation
Connector
15 pin Molex, type 03-09-2152
Weight
22
3. Technical Description
300 V
1500 V
continuous operating
see nameplate
50...60 Hz (+/- 5%)
85...110% of rated voltage
22 VA
max. 20 µA
2 mA changeable to 5 mA
1.8...2 mA or 4.5...5 mA
< 4 sec.
20% of response value
250 V AC / 24VDC
4A AC / 4A DC
4 A
2 x 10
5
cycle
continuous
C...50
C, 50
F...122
F
º
º
º
º
º
C...50
º
C, 10
º
F...122
º
F
any
approx. 1.1 lb (493gr.)
Information Request
Information Request
Questions or Comments? Just call!
Tollfree:
Customer Service, Sales andTechnical Support:
Fax:
For further information please write down:
Model:...............................................
Article No.:......................................
Serial No.:.........................................
Voltage:...........................................
Date Purchased:................................
Notes:
Thank you for purchasing a BENDER Line Isolation Monitor.
We appreciate your business.
1-800 833-6834
1-610-383-9200
1-610-383-7100
23