Menu instructions for the LIM2000plus™
Start menu
(push TEST and MUTE button
TEST
simultaneously)
TEST
Buzzer volume
Max. transformer current (optional)
Quit menu and activate parameters
MUTE
Buzzer volume
Response value of the
Sets the intensity of
load monitoring. Adjustments
the buzzer volume
in 5% steps between 10%
loud
and 100% of used CT.
,
...
quiet
(off).
MUTE
MUTE
14
2. General Information
MUTE
TEST
quit menu and
store new parameters
,
(100),
MUTE
menu
END
2. General Information
2.4
Error-Codes Listing
ER
1.0
Ground error LIM-GNDor GND interrupted
ER
2.0
AD converter calibration failed; hardware failed
error
ER
3.0
Measuring circuit test failed; hardware mistake
ER
4.0
Tolerance between actual system voltage and
calibrated system voltage has been increased
ER
4.5
Tolerance between actual signal voltage and
calibrated system voltage has been increased
ER
5.0
Hardware defect; missing system trigger
ER
6.0
Program sequence interrupted; EMI interference
ER
6.5
Program sequence interrupted; stack point
indication too high
ER
Error in the current measuring circuitry