2.2 Display
1. Amber THC setting LEDs - indicates the current "THC" setting
2. "TEST" button - checks functions of the LIM
3. Green "SAFE" LED - bright unless LIM is in alarm mode
4. LED Analog Bar Graph - displays Total Hazard Current
5. Total Hazard Current Red LED Display - displays Total Hazard
Current
6. Red "Hazard" LED - indicates "THC" >5mA (2mA)
7. Amber "MUTE" LED button silences alarm buzzer
8. Amber "Transformer Load" LED indicates transformer load over 80%
(optional)
9. Tranformer Load (TL) Red LED Display - displays transformer load
(optional)
12
2. General Information
2. General Information
2.3 Menu
To enter the menue the TEST button and the MUTE button must
be pushed simultaneously for approximately 1 second till the
buzzer begins to beep. The numeric display indicates set Point
(SP).
Now the TEST button has the function to swap upwards in the
menu.The MUTE button has the function to confirm or to activate
the selected parameters.
In the menu the following functions can be selected:
•
Sound intensity of buzzer (hi or lo)
•
Max. transformer load (100% of the transformer current)
After setting the parameters, they are stored and after leaving the
menu the LIM performs a new self test.