Autonics krn100 series Manual - Page 9
Browse online or download pdf Manual for Measuring Instruments Autonics krn100 series. Autonics krn100 series 17 pages. 100 mm hybrid recorder
Also for Autonics krn100 series: Instruction Manual (2 pages), Instruction Manual (2 pages), Product Manual (3 pages)
KRN100
٧ Two Unit
For•compound•pressure,•if•input•pressure•is•lower•than•
atmospheric•pressure(0),•it•displays•the•degree•of•a•
vacuum•with•mmHg•unit.•If•input•pressure•is•higher•
than•or•same•as•atmospheric•pressure(0),•it•displays•
positive•pressure•with••kg/cm
When•using•Two•Unit•function,•lower•limit•value•is•fixed•
as•-760mmHg•and•kg/cm
range•1•to•35.
Two•Unit•limits•scale•point•as••0•↔•0.0•↔•0.00•.•When•
using•Two•Unit,•display•unit•is•automatically•changed•
as•mmHg•or•kg/cm
The•calculation•with•Record•Method•(Data•storage•
method)•and•Filter•type•(Input•digital•filter)•is•impossible•
and•ignored•due•to•different•type•of•two•unit•value.
• • • S et•range:•1•to•35
• • • F actory•default:•-
Ex)•If•pressure•range•is•-760mmHg•to•3kg/cm
pressure•transmitter•outputs•4-20mA,•for•4mA•
input•it•displays•-760mmHg,•8mA•input•is•unit•
changing•point.•For•20mA•input,•it•displays•3kg/cm
Record zone division [ Divide Zone ]
Divides•record•zone•for•measuring•value•by•channel.•
It•divides•equally•max.•12•zones•as•equal•value.•User•
needs•to•set•record•zone•by•channel•in•Record•Zone•
setting•at•Input•Setup.•
It•is•easy•to•check•measuring•value•due•not•to•duplicated•
record•zone•with•divided•record•zone•by•channel•which•is•
set•in•Record•Zone•setting•at•Input•Setup.
If•there•is•too•many•division•for•record•zone,•record•value•
check•accuracy•is•low.•
• • • S et•range:•None,•2•to•12
• • Factory•default:•None
Ex)•SV•of•record•zone•division:•None•
Ex)•SV•of•record•zone•division:•5
Summer time [ Summer Time ]
This•function•is•for•applying•summer•time•(daylight•saving•
time)•in•specific•countries•and•regions.
When•you•set•Summer•Time,•it•adds•current•time•and•1•
hour•and•displays•the「(S)」 mark•in•front•of•the•date•and•
time•on•LCD•screen•or•in•front•of•the•date•on•recording•
paper.•
• • • S et•range:•Disable•↔•Enable
• • • F actory•default:•Disable
A-10
Series
2
•unit.
2•
value•is•able•to•set•within•set•
2
.
2
,•and•
Standard record period [ Standard Period ]
Set•record•period•to•record•current•time,•display•value•by•
channel•as•digital•number•on•recording•paper.
It•is•activated•when•Record•Mode(Record•mode)•is•Digital.
• • • S et•range:•00m•01s•to•99m•59s
• Depending•on•the•number•of•recording•channels,•min.•
set•range•is•limited•as•below.
Record•channel
1•to•2
3•to•4
5•to•6
7•to•8
9•to•10
11•to•12
• • • F actory•default:•-
Reservation record [ Reservation Type ]
2
.
This•function•is•to•set•reservation•time.•At•the•set•time,•it•
starts/stops•recording•automatically.•
You•can•select•reservation•record•either•Repeat(repeat•
ON/OFF)•or•Single(single•ON/OFF).
When•selecting•reservation•record,•'Reservation•
Period(Reservation•record•period)'•and••'Reservation•
Time(Reservation•record•time)'•are•activated.•When•
reservation•record•is•set,•the•
(recording)•or•the•
The•
•icon•tuns•OFF•when•reservation•setting•is•'Disable'.
• • Set•range:•Disable•↔•Repeat•↔•Single
• • Factory•default:•Disable
٧ Repeat (repeat ON/OFF)
From•start•recording•date•to•end•recording•date,•it•
records•data•at•from•the•set•start•time•to•the•set•end•
time.•
٧ Single (single ON/OFF)
Starts•recording•at•the•start•set•time•on•start•date•and•
finishes•recording•at•the•end•set•time•on•end•date.
File/Memory setup [ FILE/MEMORY SETUP ]
You•can•set•the•parameter•about•parameter•set•file•and•
storage•data.•Move•to•FILE/MEMORY•SETUP•with•the•
,•
••keys•,•press•the•
MEMORY•SETUP.
٧ Open parameter set file [ Load Set File ]
Applies•set•value•of•saved•parameter•set•file.••
When•applying•this•set,•backup•data,•user•unit•and•
booting•logo•are•not•changed.•
None,•Default.pms•file•is•activated•and•if•there•is•
User1.pms•to•User5.pms,•User1.pms(USB)•to•User5.
pms(USB)•file(parameter•set•save•file),•it•is•activated.
• • Set•range:•
• None•↔•Default.pms•↔•User1.pms•to•User5.pms•
↔•User1.pms(USB)•to•User5.pms(USB)
• • • F actory•default:•None
Set•range
01m•00s•to•99m•59s
02m•00s•to•99m•59s
03m•00s•to•99m•59s
04m•00s•to•99m•59s
05m•00s•to•99m•59s
06m•00s•to•99m•59s
•icon•flashes•with•the•
•(stop•recording)•icon.
•key•to•enter•FILE/