DSC Power 832 Руководство по установке - Страница 11

Просмотреть онлайн или скачать pdf Руководство по установке для Блок управления DSC Power 832. DSC Power 832 17 страниц. Central station talk / listen module
Также для DSC Power 832: Руководство по эксплуатации (11 страниц), Руководство по эксплуатации (18 страниц), Инструкция пользователя (2 страниц), Руководство по установке (12 страниц), Руководство пользователя (20 страниц), Инструкции по установке (2 страниц), Инструкции по установке (2 страниц)

DSC Power 832 Руководство по установке
M O D U L E
Depending on the type of device connected, the SYNC input must be
programmed for Normal or Inverted operation. If normal operation is
selected (default), the PC5108L will switch cameras on a low to high
transition (rising edge). If the inverted option is selected, the PC5108L
will switch cameras on a high to low transition (falling edge).
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
External/Internal Dwell Control .................. Subsection [50] Option [4]
SYNC Input Inverted/Normal ..................... Subsection [50] Option [6]
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
4.5 Module Supervision
The control panel only supervises the PC5108L when the Module
Zone Group Assignment section is programmed. When PC5015
programming section [903] Module Supervision Field is entered, the
zone lights corresponding to the zone group assignments will repre-
sent the PC5108L.
The DLM-4L is supervised when the DLM-4L Is Connected option is
enabled. This option must be enabled when using the DLM-4L. When
section [903] Module Supervision Field is entered, the DLM-4L will be
represented by zone light [23].
A Downlook Supervisory Trouble is generated when the panel no
longer detects the DLM-4L on the system. To clear this trouble, enter
Section [902] Supervision Reset. A Downlook Supervisory trouble
restoral will be logged to the event buffer when the trouble is cleared.
For information on module supervision, see the PC5015 Installation
Manual (Section 2.7 "Enable Supervision").
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Supervision Reset ............................................................ Section[902]
Module Supervision Field ............................................... Section [903]
DLM-4L Is Connected ................................ Subsection [50] Option [8]
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
O P E R A T I O N
A N D
P R O G R A M M I N G
9