9
Heatsink
4 of 8
Site Map Label
Safety Cable
SITE MAP LABEL
STEP 1:
Remove unit site map label Snap address. See
Figure 8.
STEP 2:
Apply site map label to the correct position on the site
map. See Figure 8.
INSTALLING SAFETY CABLE
NOTE: Safety Cable is sold separately as an
accessory, please refer to installation sheet in safety
cable packaging for complete installing instructions.
STEP 1:
Attach one end of the safety cable through the fin of
the heatsink. See Figure 9.
STEP 2:
Attach other end of the safety cable to mounting
surfaces using customer supplied hardware.
SYSTEM COMMISSIONING AND CUSTOMIZING
System commissioning is required for the fixtures to
be recognized on the Simply SNAP network. Contact
Cree Lighting at 800-236-6800 for more details about
commissioning and customization.
EMERGENCY DRIVER CHECK
NOTE: For short-term testing of the emergency
function, the battery must be charged for at least one
hour. The emergency driver must be charged for at
least 24 hours before conducting a long-term test.
STEP 1:
When AC power is applied, the charging indicator
light is illuminated, indicating the battery is being
charged. When power fails, the emergency driver
automatically switches to emergency power,
operating the LED array. When AC power is restored,
the emergency driver returns to the charging mode.
STEP 2:
Although no routine maintenance is required to keep
the emergency driver functional, it should be checked
periodically to ensure that it is working. The following
schedule is recommended:
• Visually inspect the charging indicator light
monthly. It should be illuminated.
• Test the emergency operation of the fixture at
30-day intervals for a minimum of 30 seconds.
When the test switch is depressed, the LED
array should operate.
• Conduct a 90-minute discharge test once a
year. The LED array should operate for at least
90 minutes.
If the luminaire fails any of these checks, consult
service personnel.
REFER ANY SERVICING INDICATED BY THESE
CHECKS TO QUALIFIED PERSONNEL
EMERGENCY DRIVER AND AC DRIVER MUST BE
FED FROM THE SAME BRANCH CIRCUIT.