Output LOAD In Buffer Mode (Mains INPUT OFF)
Some example of buffering time depending on LOAD Output in function to the Ah of the battery.
Buffering Time
Load 1.5 A
Load 3 A
Load 5 A
Load 7.5 A
Load 10 A
Load 12 A
Load 15 A
Load 20 A
Operating and Display Element:
No. 10: INPUT Mains AC Port pin L – N:
1 Phase Switching Power Supplies PE
No. 3: BATTERY Connection Port:
Connect the battery to the BATTERY (-) and (+)
One battery (12 Vdc) for 12V
Two battery (12 Vdc) connected in Series for 24V
No. 4: Output LOAD:
Connect this Output to the LOAD (-) and (+)
No. 1, 2 Signal Ports (output Isolated):
Connections for
No. 2: MAINS OR BACKUP: Input Mains On/Off. Contact: 5,6,7
No. 1: BATTERY FAULT Fault connections systems. Contact: 8,9,10
Relay Contact Rating:
Max.DC1: 30 Vdc 1 A; AC1: 60 Vac 1A : Resistive load (EN 60947-4-1)
Min.1mA at 5 Vdc: Min. permissive load
Signal Output port true table:
MAINS Input Vac
The BATTERY in
BACKUP it's less than
30% cap?
BATTERY or system
FAULT?
Note:
(1) For better efficiency of the system, filter relay MAINS OR BACKUP with a delay of at least 5 seconds before give
alarm Mains Lost, example: connection to PLC.
(2) See Diagnosis Led
BATT1.2 Ah BATT 3 Ah
20 min
60 min
8 min
30 min
3 min
15 min
2 min
10 min
No
7 min
No
3 min
No
No
No
No
3
4
6
7
8
12
9
13
10
Led N°6 MAINS OR BACKUP
5-6 Closed
ON
■ - led off
OFF
YES
NO
YES
■ - led off
NO
■ - led off
BATT7.2 Ah
BATT12 Ah
200 min
400 min
120 min
240 min
55 min
100 min
30 min
60 min
20 min
45 min
12 min
30 min
9 min
20 min
7 min
13 min
2
1
19
5
17
11
14
16
15
18
L N
Port N°2
5-7 Closed
■ - led On (1)
■ - led On
■ - led On
BATT100 Ah
/
/
/
/
20 h
600 min
400 min
240 min
Port N°1
Led N°7 BATTERY FAULT
8-9 Closed OK
8-10 Closed
■ - led off
■ - led off
■ - led On
■ - led off
■ - led On (2)
■ - led off