- ページ 5
電源 ADELSYSTEM CBI-1280 SeriesのPDF マニュアルをオンラインで閲覧またはダウンロードできます。ADELSYSTEM CBI-1280 Series 11 ページ。 All in one dc ups power solutions
No. 6, 7 and 8 Display Signals
No.6: Led MAINS OR BACKUP: Input Mains On/Off
No.7: Led BATTERY FAULT (capacity less than 30%), Fault connections systems, Battery replacement.
No.8: Led DIAGNOSIS Battery charge mode, diagnosis of the system through "blinking code" signal.
Monitoring
Control
State
Chart:
Trickle
Charging
Absorption
Type
Boost
Recovery
Reverse polarity or high battery Voltage (over 32.5Vdc for
24V)
Battery No connected
Element in Short Circuit
Over Load or short circuit on the load
Auto
Bad battery; Internal impedance Bad or Bad battery wire
diagnosis
connection.
of the
Life test not possible
system
Bad thermal sensor
Boost condition; battery discharge after 4 min. of overload. 8 Blink/pause
Internal fault or illegal configuration jumper
Low battery (under 18.5Vdc for 24V) Only if started from
battery, no Main input. Form Input N°12 or Push Bottom
MOD BUS error
No. 9, 12: BATTERY START, No MAINS Vac
No. 9: Push-button, for 3 sec., in the front panel for switch ON the system without the "MAINS input Vac" but
only the battery connected.
No.12: It is also available the same function for remote Start from the battery, via RTCONN cable with 2
poles connector to put in Input N°12 and use with a Push button or a normaly open contact. Do not insert a
jumper in this position, penalty discharge completely the battery close to Zero in BACKUP.
No. 17: Battery Management Configurations
One device for all battery types.
Completely automatic, all devices are suitable to charge most
batteries types thank to User Selectable charging curves. They can
charge open lead acid, sealed lead acid, Gel and Ni-Cd batteries. It
is possible to change or add other charging curves connecting the
device to a portable PC.
Caution: Switch off the system before Setting the jumper.
For Battery Type Selection always refer to the data of the
Battery Type
Selection
Open Lead
VRLA (AGM) "1"
Gel Battery "2"
Ni-Cd "3"
(1)
Deep Switch Position
BATTERY TYPE
BATTERY TYPE
BATTERY TYPE
BATTERY TYPE
Point of view
manufacturer of the batteries.
Trickle/Float
charge
(Volt/Cell)
2.23
2.25
2.30
10% Imax Trimmer
LED Diagnosis
(No.8)
1 Blink/2 sec
1 Blink/sec
2 Blink/sec
5 Blink/sec
1 Blink /pause
2 Blink/pause
3 Blink/pause
4 Blink/pause
5 Blink/pause
6 Blink/pause
7 Blink/pause
9 Blink/pause
10 Blink/pause
11 Blink/pause
BATTERY TYPE
LIFE TEST
ENABLE POWER SUPPLY
Fast/Bulk charge
(Volt/Cell)
2.40
2.40
2.40
1.70–(12V);1.5–(24V)
LED Battery
Fault (No.7)
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON