DFE SW6 Operating Instructions Manual - Page 11
Browse online or download pdf Operating Instructions Manual for Controller DFE SW6. DFE SW6 20 pages. Digital tension controller
2
OPERATING INSTRUCTIONS
2.1 BASIC OPERATION
When the controller has been properly set up and the control loop has been tuned, it should maintain
constant tension while the machine is running and while speed, roll diameter, or other conditions change.
However, during startup of a new roll you may want to change modes, setpoint or other settings. Usually,
the only thing the operator will need to do is turn tension On or Off, toggle between Auto and Manual
modes, and change the Auto tension setpoint or Manual output setting.
With tension off, to turn tension on and enable output, press the tension On / Off button. If the controller
is in Auto mode, the output will ramp up or down to tension the web to the Auto Tension Setpoint. If the
controller is in Manual mode, the output will change to the manual output setting. Either the auto or manual
mode will be indicated as active by the Auto / Man status indicator in the upper right hand corner of the
display. The Auto and Manual modes can be toggled back and forth by pressing the Auto / Man button.
While in either auto or manual mode, the "+" and "-" buttons for adjusting the auto tension setpoint or the
manual output setting can be brought up by touching the tension display screen.
2.2 DISPLAY ADJUSTMENTS
Operator-adjustable display settings described
below may be found and adjusted at Menu > Main
Menu > Operator Menu > Display Configuration
(Fig. 7). Adjustments to these settings may be
made using the up and down arrows, and then
saved by pressing the SAVE button. These
adjustments serve visual purposes only, and do
not affect the control loop.
• Tension Update - Choose 0.2, 0.5, 1.0, 2.0 or
5.0 seconds and press SAVE to adjust the time
it takes for the display to update with new
information. Longer updates produce fewer
changes in displayed information over time, at
the expense of rapid visual response to
changes in tension.
• Display Damping - Choose 0.0, 0.2, 0.4, 0.8, 1.6 or 3.2 sec and press SAVE to adjust how smoothly
information is displayed.
• Plot Update Time - Choose 30 sec or 1, 2, 5, 10 or 30 min and press SAVE to adjust time that tension
displays before dropping off the trend-line graph screen. This also applies to the PID tune screen
referenced repeatedly in the Technical Reference Manual (DFE P/N 801-2540).
• Line Speed Display - Choose Auto, On or Off and press SAVE. When in Auto, if line speed is required
for control, it will be displayed by default. Otherwise, either On or Off may be chosen to force the display
of line speed or to suppress it.
• Diameter Display - Choose Auto, On or Off and press SAVE. When in Auto, if the roll diameter is
required for control, it will be displayed by default. Otherwise, either On or Off may be chosen to force
the display of roll diameter or to suppress it.
• Display Brightness - Adjust between 10% and 100% and press SAVE to control the brightness of the
display.
2.3 SAVING, RECALLING AND DELETING SETUPS
An Active Setup is composed of all the most recently selected settings and is held in non-volatile memory,
meaning that even if power is lost, the settings will not be. The active setup is not recalled using the
named setups, but will automatically come up again upon restart if the controller is shut down while
operating in that setup.
Figure 7 - DISPLAY CONFIGURATION MENU
5