PAN-10 and PAN-12 Sensor installation guide
Sensor specifications
Specifications
Physical dimensions
Max hot-air outer diameter
(including insulation)
Current measurement
range
Current measurement
accuracy (typical, at 25° C)
Minimum operating current 0.3 – 0.45 A
AC frequency supported
Transmission frequency
Transmission power (ERP)
Transmission interval
Safety and
EMC certificates
Flammability rating of
external enclosure
Operating temperature
Storage temperature
Revision 1.4 January 2018
© 2018 Centrica plc. Registered office: Millstream, Maidenhead Road, Windsor, Berkshire. SL4 5GD.
Registered in England & Wales No 3033654
PAN-10
17 x 20 x 32 mm
0.67 x 0.79 x 1.26 inch
7 mm
0.28 inch
0-63 A
<2% at I>1A
50 Hz (EU, JPE)
60 Hz (US, JPW)
434 MHz (EU)
902-928 MHz (US)
923 MHz (JPE, JPW)
0 dBm (Max)
-4 dBm (Max JPE, JPW)
10 seconds
USA & Canada
Safety: UL-61010-1,
CSA-C22.2 (ETL listed)
EMC/Radio: FCC Part 15
subpart B, C
Europe
Safety: EN-61010-1 (CE)
EMC: EN-ETSI 301489-3,
Radio: EN-ETSI 300220-1
Japan
Radio: ARIB STD-T108
UL94 V-0
0-50° C
-20-65° C
PAN-12
46.2 x 22.8 x 32.6 mm
1.82 x 0.90 x 1.28 inch
18.8 mm
0.74 inch
0-225 A
<2% at I>10A
0.5 – 0.8 A
50 Hz (EU, JPE)
60 Hz (US, JPW)
434 MHz (EU)
902-928 MHz (US)
923 MHz (JPE, JPW)
0 dBm (Max)
-4 dBm (Max JPE, JPW)
10 seconds
USA & Canada
Safety: UL-61010-1,
CSA-C22.2 (ETL listed)
EMC/Radio: FCC Part 15
subpart B, C
Europe
Safety: EN-61010-1 (CE)
EMC: EN-ETSI 301489-3,
Radio: EN-ETSI 300220-1
Japan
Radio: ARIB STD-T108
UL94 V-0
0-50° C
-20-65° C